Warning, Horizontal termination, Joining pipe and fittings – Bryant 4-WAY MULTIPOISE 359AAV User Manual

Page 28

Advertising
background image

28

Rubber Coupling
& Clamps

90

° Elbow

Combustion
Blower

Vent Fitting
& Clamps

Vent Extension
Pipe (Side Panel
Exit)

Vent Pipe
(Top Panel Exit)

Vent Pipe

Rotate downward
5

° to 10°

NOTE: Built--in channel will be angled 5

° to 10° also.

SIDE VIEW

NOTE: The 90

° elbow is approved

for use inside the furnace ONLY.

Tee

A07714

Fig. 20 -- Proper Sealing Procedure for Combustion Blower

Joining Pipe and Fittings

SEE VENT AND COMBUSTION AIR PIPING, vent and

Combustion Air Piping Guidelines in this manual for applicable

ASTM Standards for vent materials.

FIRE HAZARD
Failure to follow this warning could result in personal injury,

death, and/or property damage.
Observe all cautions and warnings printed on material

containers.
Provide adequate ventilation and do NOT assemble near heat

source or open flame. Do NOT smoke while using solvent

cements and avoid contact with skin or eyes.

!

WARNING

CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or

death.
Do NOT use solvent cement that has become curdled, lumpy

or thickened and do NOT thin. Observe precautions printed

on containers. For applications below 32_F (0_C), use only

low temperature type solvent cement. Poor joints may lead to

disconnected or leaking vent pipe joints allowing carbon

monoxide to enter the living space.

!

WARNING

1. Cut pipe end square, remove ragged edges and burrs.

Chamfer end of pipe, then clean fitting, socket and pipe

joint of all dirt, grease, or moisture.

NOTE: Stir the solvent cement frequently while using. Use a
natural bristle brush or the dauber supplied with the cement. The
proper brush size is one inch.

2. After checking pipe and socket for proper fit, wipe socket

and pipe with cleaner-primer. Apply a liberal coat of

primer to inside surface of socket and outside of pipe. Do

NOT allow primer to dry before applying cement.

3. Apply a thin coat of cement evenly in the socket. Quickly

apply a heavy coat of cement to the pipe end and insert

pipe into fittings with a slight twisting movement until it

bottoms out.

NOTE: Cement MUST be fluid while inserting pipe. If NOT,
recoat pipe.

4. Hold the pipe in the fitting for 30 seconds to prevent the

tapered socket from pushing the pipe out of the fitting.

5. Wipe all excess cement from the joint with a rag. Allow 15

minutes before handling. Cure time varies according to fit,

temperature and humidity.

Connecting Vent Pipes and Termination

(Direct Vent)

NOTE: For direct vent applications, combustion air intake and
vent MUST terminate in the same atmospheric pressure zone. If
installation is in a cold climate (sustained temperatures 0°F

(--18°C)and below for 24 or more consecutive hours), increase

the minimum distance between vent pipe and air intake from 8″

to 18″ (203 to 457 mm).

1. Install all couplings, nipples and elbows using proper pro-

cedures for Joining Pipe and Fittings and maintain spa-

cing between vent and combustion air piping as indicated

in Fig. 21 through Fig. 23.

8” 203.2mm* MIN.

20’(6.1m) MAX

8” (203.2mm)

MIN.

*18 in. (457.2mm) Minimum for
cold climates (sustained tem-
peratures 0

°F(-17°C) and below

for 24 or more consecutive
hours)

GRADE LEVEL

OR

12 ”

(304.8mm)

MIN.

EXHAUST

INLET

A07715

Fig. 21 -- Sidewall Termination 12” (305 mm) or More Above

Snow Level or Grade Level

Horizontal Termination

1. Cut two holes. 2--

1

/

2

″ (64 mm) for 2″ (51 mm) pipe, 3″ (76

mm) for 2--

1

/

2

″ (64 mm) pipe, or 3

1

/

2

″ (89 mm) for 3″ (76

mm) pipe. Do NOT make the holes oversized, or it will be

necessary to add a sheet metal or plywood plate on the

outside with the correct size hole in it.

2. Check hole sizes by making sure it is smaller than the

couplings or elbows that will be installed on the outside.

The couplings or elbows MUST prevent the pipe from be-

ing pushed back through the wall.

3. Extend vent pipe and combustion air pipe through the wall

3

/

4

″ (19 mm) to 1″ (25 mm) and seal area between pipe

and wall.

4. Install the couplings, nipple and termination elbows as

shown and maintain spacing between vent and combustion

air piping as indicated in Fig. 21 and Fig. 22.

A metal shield is recommended 18″ x 18″ (457 mm x 457 mm)

min. or 18″ (457 mm) min. diameter around the vent termination

at the exterior wall to protect the house exterior materials from

flue product or condensation (freezing) damage.

359AA

V

Advertising