Horizontal right through top (see fig. 17) – Bryant 4-WAY MULTIPOISE 359AAV User Manual

Page 25

Advertising
background image

25

Cut Here

Drain Tube Corrugated

5

/

8

″″ ID & Clamps

Cut at straight section

Leave room for clamp

IN

ON

OF
F

V

E

N

T

Relief Tube Rubber Tube

3

/

16

ID

Trap Connection

“Clamp ears”
Pointed OUT

Preassemble &
insert into furnace

Single Pressure Switch Detail

Dual Pressure Switch

Tee Trap
White PVC
(loose parts bag)

WARNING
Add Cap and
Clamp

Flexible Tubing Connector

3

/

16

OD (Loose Parts Bag)

Drain Tube Black Rubber

1

/

2

ID & Clamps

EXHAUS

T

Alternate Orienta-
tion

Field
Supplied Tee

Relief Tube Extension
Black Rubber

3

/

16

ID

Cut to Fit (Loose Parts Bag)

Plastic Cap
Yellow or black

Vent Drain
& Clamps

INLET

On Some Models
ONLY

Coupling & Clamps
(Optional)

AIRFLOW

Barbed Coupling

1

/

2

OD

(Loose Parts Bag)

Elbow Tube Black Rubber

1

/

2

ID & Clamps (Loose Parts Bag)

Representative drawing only, some models may vary in appearance.

A07711

Fig. 17 -- Horizontal Right through Top

Horizontal Right through Top (See Fig.

17)

S

Disconnect the hoses from the trap assembly, and remove trap
and trap mounting bracket from the blower compartment.
Using cover plate and gasket provided in the loose parts bag,
cover the hole from the burner compartment to the blower
compartment and secure with screws.

S

Remove knockout from the side of the furnace casing where
drain tube will exit.

S

Mount the trap externally to the bottom side of the unit using
the 2 screws provided in the location shown.

S

Cut the corrugated tube as shown in the illustration above.
Connect the corrugated hose from the transition to the trap.
Secure connections with clamps.

S

Connect the black

1

/

2

″ (13 mm) ID drain tube from the Vent

Drain to the trap. If an extension is required, use the black

1

/

2

(13 mm) OD barbed coupling and the black

1

/

2

″(13 mm) ID

drain tube in the loose parts bag. Cut tube to length. Secure
connections with clamps.

S

Connect the

3

/

16

″ (5 mm) ID relief tube to the middle port on

the trap. If an extension is required, use the clear

3

/

16

″(5 mm)

OD flexible tubing connector and the black

3

/

16

″(5 mm) ID

relief tube in the loose parts bag. Cut tube to length.

S

Cut an appropriate length of 2″ (51 mm) PVC pipe, fittings
and extension pipe long enough to exit the cabinet and connect
the vent drain to a standard field supplied 2″ (51 mm) PVC tee

S

Install tee trap into bottom section of tee.

S

Connect the tee trap and the main drain line exiting the casing
as shown in Fig. 19.

NOTE: It is recommended that all PVC piping and fitting
connections be fit up and inspected before final cementing. Both
the external trap and the external tee trap must be primed before
operation. Verify all condensate drain connections are securely
clamped. A coupling and clamps (in loose part bag) may be
installed as shown for future servicing of the vent system.

359AA

V