Horizontal left--side vent (see fig. 16) – Bryant 4-WAY MULTIPOISE 359AAV User Manual

Page 24

Advertising
background image

24

AIR FLOW

IN

ON

OFF

V

E

N

T

Relief Tube Black Rubber

3

/

16

ID

25--24--88

Single Pressure Switch Detail

Dual Pressure Switch

Tee Trap White PVC
(loose parts bag)

WARNING
Move Caps to top of trap

Flexible Tubing Connector

3

/

16

OD (Loose Parts Bag)

Elbow Tube Black Rubber

1

/

2

ID & Clamps

(Loose Parts Bag)

EXHAUS

T

Alternate Orientation

Field
Supplied Tee

Cut Here

Cut at straight section

Leave room for clamp

Relief Tube Extension
Black Rubber

3

/

16

ID Cut to Fit

(Loose Parts Bag)

Yellow or black
Plastic Cap

Vent Drain
& Clamps

Level or Sloped towards Tee

INL

E

T

On Some
Models ONLY

Drain Tube Black,

5

/

8

ID Corrugated

Drain Tube Black Rubber

1

/

2

ID & Clamps

Barbed Coupling

1

/

2

OD (Loose Parts Bag)

Representative drawing only, some models may vary in appearance.

A07710

Fig. 16 -- Horizontal Left--Side Vent

Horizontal Left--Side Vent (See Fig. 16)

S

Remove the drain tee from the Vent Drain if installed.

S

Rotate the inducer 180

°

for a side vent after loosening the 4

inducer attachment screws. Reinstall and retighten the inducer
screws to 20″ (2.26 newton meters) pounds torque.

S

Disconnect the hoses from the trap assembly, and remove trap
and trap mounting bracket from the blower compartment.
Using cover plate and gasket provided in the loose parts bag,
cover the hole from the burner compartment to the blower
compartment and secure with screws.

S

Remove knockout from the side of the furnace casing where
drain tube will exit.

S

Mount the trap externally to the bottom side of the unit using
the 2 screws provided in the location shown.

S

Cut the corrugated tube as shown in the illustration above.
Connect the corrugated hose from the transition to the trap.
Secure connections with clamps.

S

Connect the black

1

/

2

″(13 mm) ID drain tube from the Vent

Drain to the trap. If an extension is required, use the black

1

/

2

″(13 mm) OD flexible tubing connector and the black

1

/

2

″(13 mm) ID drain tube in the loose parts bag. Cut tube to

length. Secure connections with clamps.

S

Connect the

3

/

16

″(5 mm) ID relief tube to the middle port on

the trap. If an extension is required, use the

3

/

16

″OD flexible

tubing connector and the black

3

/

16

″(5 mm) ID relief tube in

the loose parts bag. Cut tube to length.

S

Cut an appropriate length of 2″ (51 mm) PVC pipe, fittings
and extension pipe long enough to exit the cabinet and connect
the vent drain to either:

— A standard field supplied 2″ (51 mm) PVC tee, or
— A 2″ (51 mm) PVC coupling fastened onto the drain

tee.

S

Install tee trap into bottom section of tee.

S

Important: The pipe to the tee trap must be level or sloping
towards the tee trap

S

Connect the tee trap and the main drain line exiting the casing
as shown in Fig. 19.

NOTE: It is recommended that all PVC piping and fitting
connections be fit up and inspected before final cementing. Both
the external trap and the external tee trap must be primed before
operation. Verify all condensate drain connections are securely
clamped. A coupling and clamps (in loose part bag) may be
installed as shown for future servicing of the vent system.