7. Install a manual shut--off valve external to furnace casing

and tighten all joints securely.

8. If local codes allow the use of flexible gas appliance con-

nectors, always use a new listed connector.

Do not use a connector which has previously serviced an-

other gas appliance.

9. Flexible corrugated metal gas connector may NOT be

used inside the furnace or be secured or supported by the

furnace or ductwork.

10. Properly size gas pipe to handle combined appliance load

or run gas pipe directly from gas meter or Propane gas reg-

ulator.

11. Install correct pipe size for run length and furnace rating.

12. Measure pipe length from gas meter or Propane second

stage regulator to determine gas pipe size.

Additional Propane Connection

Requirements

1. Have a licensed Propane gas dealer make all connections

at storage tank and check all connections from tank to fur-

nace.

2. If copper tubing is used, it MUST comply with limitation

set in National Fuel Gas Code or CGA codes.

3. Two--stage regulation of Propane gas is recommended.

Propane Conversion

FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal injury or

death.
A Propane conversion accessory kit is required when

operating the furnace with Propane gas.

!

WARNING

An accessory kit shall be used to convert to propane gas use, see

the furnace rating plate for the Propane conversion accessory kit

part number.

Supply Pressure

FIRE HAZARD
Failure to follow this warning could result in personal injury or

death.
Do NOT set input rating above that shown on rating plate.

!

WARNING

1. A

1

/

8

″ NPT plugged tapping, accessible for a test gauge

connection, must be installed immediately upstream of the

gas supply connection to the furnace.

2. Gas input to burners MUST NOT exceed the rated input

shown on rating plate.

3. Do NOT allow minimum gas supply pressure to vary

downward. Doing so will decrease input to furnace. Refer

to Table 6 and 7 for normal gas supply and manifold

pressures.

Manifold Gas Pressure Adjustment

SEE CHECKS AND ADJUSTMENTS, Manifold Gas

Pressure Adjustment in this manual.