Vertical termination, Multi vent termination clearances – Bryant 4-WAY MULTIPOISE 359AAV User Manual

Page 30

Advertising
background image

30

Vertical Termination

1. Fig. 24 shows the proper installation and clearances for

vertical vent termination. The vertical roof termination

should be sealed with a plumbing roof boot or equivalent

flashing. The inlet of the intake pipe and end of the ex-

haust vent must be terminated no less than 12″ (305 mm)

above the roof or snow accumulation level, and 12″ (305

mm) away from a vertical wall or other protrusion.

2. If the vent system is installed in an existing chimney make

sure clearances shown in Fig. 23 are maintained. Horizont-

al section before the termination elbow can be extended on

the inlet air to provide necessary clearance.

Multi Vent Termination Clearances

When two (2) or more furnaces are vented near each other, each

furnace must be individually vented.
Two (2) vent terminations may be installed as shown in Fig. 25,

26, 27, 28 and 29, but the next vent termination must be at least

36″ (914 mm) away from first 2 terminations. It is important that

vent terminations be made as shown to avoid recirculation of flue

gases.

Combustion
Air

Exhaust

12

in. (304.8mm)

Min. Grade or
Snow Level

36” Min.

2” (50.8mm) Max.

36” Min.

OR

(914.4mm)

(914.4mm)

A07718

Fig. 25 -- Concentric Vent and Combustion--Air

Roof Termination

“A”

Vent

Dimension “A” is touching or 2 in. (503.8mm) maximum separation.

25--22--02d

Vent

Combustion Air

Exhaust

1 in. (25.4mm)
Maximum

A07695

Fig. 26 -- Concentric Vent and Combustion Air

Sidewall Termination

Exhaust

“A”

“A”

Inlet

Dimension “A” is touching or 2 in. (50.8mm) maximum separation

8 in. (203.2mm)
Min.

18 in. (457.2mm) Min. for Cold Climates
[Sustained 0

°F(-17 °C) and below for

24 hours or more consecutive hours]

12 in. (304.8mm) Min.
Grade or Snow Level

8 in. (203.2mm) Min.
20 in. (6.1m) Max.

A07696

Fig. 27 -- Sidewall Inlet Vent and Exhaust--Air Termination

Exhaust

Inlet

“A”

“A”

Dimension “A” is touching or 2 in. (503.8mm) maximum separation.

18 in. (457.2mm) Min. for Cold Climates
[Sustained 0

°F(-17°C) and below for

24 hours or more consecutive hours]

8 in. (203.2mm) Min.
20 in. (6.1m) Max.

8 in. (203.2mm) Min.

12 in. (457.2mm)
Min. Grade or
Snow Level

A07697

Fig. 28 -- Sidewall Inlet Vent and Exhaust--Air Termination

with Exterior Risers

Exhaust

25--22--43

Inlet

12 in. (304.8mm)
Min. Grade or
Snow Level

18 in. (457.2mm) Min. for Cold Climates
[Sustained 0

°F(-17°C) and below for

24 hours or more consecutive hours]

8 in. (203.2mm) Min.
20 in. (6.1m) Max.

A07698

Fig. 29 -- Rooftop Inlet Vent and Exhaust--Air Termination