1 alarm, 13 configuration – JUMO 705060 mTRON T - Multifunction Panel 840 Operating Manual User Manual
Page 142

13 Configuration
142
13.7.1
Alarm
Limit value monitoring with one or two alarms can be activated for each integer variable. The
alarm is entered in the status and title line and in the alarm and event list of the multifunction
panel.
This type of limit value monitoring is in addition to and independent of the limit value monitoring
of the base unit.
Setup dialog
Parameter
Parameter
Selection/settings
Description
Alarm type 1, 2
Inactive
Monitoring is not active.
Min. Alarm
Alarm is issued if the limit value is not
met.
Max. Alarm
Alarm is issued if the limit value is
exceeded.
Limit value 1, 2
-99999 to 0 to +99999
Limit value at which an alarm is issued.
Alarm text 1, 2
Use default text or enter other text.
Text that is displayed or entered in the
status and title line and in the alarm list
and event list in the case of an alarm.
Switching differ-
ential
0 to 99999
Used to reject constant switching opera-
tions in the event of minor fluctuations of
the input signal around the limit value
Alarm rejection
Inactive
Digital selector
Signal for activating the alarm rejection
Alarm delay
0 s to 65535 s
Delay time for alarm triggering
?
?