7 configuration – JUMO 701550 di 308 - Digital Indicator Operating Manual User Manual
Page 36

7 Configuration
36
Linearization
LINEAR
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
Linear
Pt100 DIN
Pt500 DIN
Pt1000 DIN
KTY11-6
Pt100 GOST
Pt 50 GOST
Cu100
Cu50
Chromel-Copel
W5Re-W26Re C
W3Re-W25Re D
NiCr-Con E
Cu-Con T
Fe-Con J
Cu-Con U
Fe-Con L
NiCr-Ni K
Pt10Rh-Pt S
Pt13Rh-Pt R
Pt30Rh-Pt6Rh B
NiCrSi-NiSi N
W3Re-W26Re
Customised linearization
For customised linearization, a maximum of 10
knee points can be implemented, or a 4th order
polynomial function programmed (only
through
the setup program).
For the „KTY11-6“ linearization, the resistance
is 2k
Ω
at 25°C (setting only through the setup
program and with 2-wire circuit).
Measurement
offset
OFFSET
-19999…
0…
99999
The measurement offset is used to correct a
measured value by a certain amount upward or
downward. Examples:
Measured displayed
value
offset
value
294.7
+0.3
295.0
295.3
-
0.3
295.0
To enter digits after the decimal point, the value
of system point must be set accordingly (see
page 57).
Special case: „2-wire circuit“
If the input is connected to an RTD temperature
probe in 2-wire circuit, then the lead resistance
is set in ohms here.
➔ INPUT1 (analog input 1) ➔
➔ INPUT2 (analog input 2) ➔
Parameter
Value/
Selection
Description
Factory settings are shown bold.