7 Configuration
➔ OUTANALG (analog outputs) ➔ Output 5 ➔
➔ Output 6 ➔
➔ Output 7 ➔
Parameter
Value/
Selection
Description
Function
F U N C T I O N (analog
selector)
deactivated
Function of the output
Type of signal
S I G N A L
0
1
2
3
0...10V
2...10V
0...20mA
4...20mA
Physical output signal
Range error
R A N G E R R 0…101
Output signal (in % of the value range) for
an overrange or underrange.
101=last output signal
Scale low point
S C A L - L O W -19999…
0…
99999
A value range of the output variable is
assigned to a physical output signal. The
ex-factory setting corresponds to an output
variable with a value range of 0...100.
Example:
Via an analog output (0 … 20mA), a
temperature ranging between 150 … 500°C
is to be output.
i.e.: 150 … 500°C
־ 0 … 20mA
Scale low point: 150 / Scale high point: 500
Scale high point SCAL-HI
-19999…
100…
99999
Offset
(Setup)
-19999…
0…
99999
The offset is used to correct the output
signal by a certain amount upwards or
downwards.
Examples:
Original
Output
value
Offset
value
294.7
+0.3
295.0
295.3
-
0.3
295.0
To enter digits after the decimal point, the
value of system point must be set
accordingly (see page 57).
Adjustment only possible in the setup
program:
-> Outputs -> Analog outputs
Factory settings are shown bold.