Diagnostics

9.1

LED status displays of the MC-PND communication card

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.1

LED status displays of the MC-PND communication card

[9-1]

LED status displays of the MC-PND communication card

MC-PNx-001_LED

ACTIVE

LINK

PROFINET

SYS

ST0

ST1

ST2

LED

Colour

Status

Description

SYS

Green

On

Operating system is running

Yellow

Blinking once per

second (1 Hz)

Error during boot process

On

Boot loader waits for boot process

-

Off

No voltage supply or hardware is defective.

ST0

Red

On

System error: Watchdog timeout

Channel, generic or extended diagnostics is available.

Blinking 2 times per

second (2 Hz)

DCP signal is triggered via fieldbus.

Off

No error

ST1

Red

On

No configuration or too slow physical connection or no physical

connection

Blinking 2 times per

second (2 Hz)

No data exchange

Off

No error

ST2

-

-

No function

Link

Green

On

Connection to Ethernet has been established.

Off

No connection to Ethernet

Active

Yellow

Blinking

Device transmits/receives Ethernet frames