8

CMVLC401A

Commissioning

4

Parameters for use with RS-485/LECOM

4.1

Drive Communication Parameters

The parameters listed in Table 5 are always present on the drive, even if there is no communication module installed.

Table 5: Drive Communication Parameters

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

P400

Network Protocol

0 Not Active
1 Remote Keypad
2 Modbus RTU
7 LECOM-B

P401

Module Revision

01.0.0 Display reads 01.x.x where:

01 = RS485/Remote Keypad Module
x.x = Module Revision

Read only

P402

Module Status

0

0 Not Initialized

Read only

1 Initialization: Module to EPM
2 Initialization: EPM to Module
3 Online

the communications between the drive
and module are working properly.

4 Failed Initialization Error
5 Time-out Error
6 Initialization Failed

Module type mismatch ( 0 )

7 Initialization Error

Protocol Selection mismatch ( 0 )

P403

Module Reset

0

0 No Action
1 Reset Module parameter values to
default.

Returns module parameters 401…499 to
the default values shown in this manual.

P404

Module Time-out
Action

3

0 Ignore

• Action to be taken in the event of an

SPI Time-out.

• SPI Time-out is fixed at 200ms.

1 STOP (refer to 11 )
2 Quick Stop
3 Fault ( n )

P405

Network Fault

0

0 No Fault

Read only, see P425 and P426

1 Network Time-out, F

P406

Proprietary

Module specific

Read only

NOTE:
If this parameter returns a value of 16, the software version in this SMVector drive
does not support the LECOM functionality. Contact factory technical support.

P498

Missed Messages
Drive to Module

Read only

P499

Missed Messages
Module to Drive

Read only