Commissioning – Lenze SMVector RS-485 LECOM User Manual

Page 23

Advertising
background image

21

CMVLC401A

Commissioning

Code
Number

Parameter Name

Default Range of Adjustment

Important

C0150

Controller Status
Word

Bit

Description

Read only

0

Reserved

1

Power stage transistors energized

2

Current Limit reached

3

Reserved

4

Setpoint Frequency reached

5

Actual frequency above threshold C17

6

Actual frequency == 0Hz

7

Controller inhibit
0 = No controller inhibit
1 = Controller inhibit

8 - 11 Controller status

0 = No error
1 = Error

12

Overtemperature fault

13

DC Bus overvoltage

14

Direction of rotation
0 = CW
1 = CCW

15

Read for operation
0 = fault (not ready for operation)
1 = no fault (ready for operation)

LECOM Format = VH

Advertising