Commissioning – Lenze SMVector RS-485 LECOM User Manual

Page 11

Advertising
background image

9

CMVLC401A

Commissioning

4.2

RS485 LECOM-Specific Parameters

The parameters listed in Table 6 are only present in the drive if there is an RS485 communication module installed,
P400 = 7 and the module is online (P402 = 3).

Table 6: RS485 LECOM-Specific Parameters

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

P410

Network address

1

1

99

The values 00, 10, 20, 30 … 90 must not
be used since they are reserved for group
addressing (see section 6.4).

P411

Network
Baud Rate

0

0 9600 bps
1 4800 bps
2 2400 bps
3 1200 bps
4 19200 bps

P420

Network Control
Level

0

0 Monitor Only

P420 =2, 3: setpoint control using code
number C0046 or C1061.
P420 = 3, 4: drive control using code
numbers C0040 and/or C0135
P420 = 4: setting C0140 = 0 results in
Quick Stop
Stop commands (QUICK STOP, INHIBIT)
will always be accepted.

1 Parameter Programming
2 Programming and Setpoint Control
3 Full Control
4 Full Control (Special)

P424

Network Powerup
Start Status

0

0 Quick Stop
1 Controller Inhibit

P425

Network Message
time-out

50

0

{ms}

65000

P426

Network Message
time-out action

0

0 No action
1 Controller Inhibit
2 Quick Stop
3 Trip Fault, F.nF1

P427

Valid Network
messages
Received

0

0

{messages} 9999

• Read-only
• When number of messages exceed

9999, counter resets and resumes
counting from 0.

P494

Communication
Module software
version

• Read only
• Format: x.yz

P495

Internal Code

• Read only
• Alternating Display: xxx-; -yy