Drive Registers

8.1

Configuration and Control Registers

Registers #1 through #1099 are reserved for registers that are only available over the network and cannot be accessed
via the drive’s local keypad.

Table 9: Configuration & Control Registers

Code
Number

Parameter Name

Default Range of Adjustment

Important

C0040

Controller Inhibit

0

0 Controller inhibited
1 Controller enabled

The controller can also be enabled
with the control word C0135

C0043

Fault Reset

0

0 No Action
1 Reset Fault

The fault can also be reset with
the control word C0135

C0046

Frequency Setpoint

0.0

…

500.0 Hz

Read only

C0050

Actual Output
Frequency

0.0

…

500.0 Hz

Read only

C0068

Operating Status Bit
Word

Bit

Description

Read only

0-3

The 10th digit of the LECOM fault number is
displayed. Example:
TRIP OH = 5 (LECOM no. = 50)

4-7

Last communication error
0 = No fault
1 = Check sum error
2 = Protocol frame error
3 = Reserved
4 = Invalid code number
5 = Invalid variable
6 = No access permission
7 = Telegram processing interrupted by a new
telegram
15 = General fault

8

Control via LECOM enabled

9

Actual frequency above threshold C17

10

Direction of rotation
0 = CW
1 = CCW

11

Power stage transistors energized

12

Quick STOP active

13

Current Limit

14

Setpoint frequency reached

15

Fault occurred

LECOM Format = VH