Commissioning 8 drive registers – Lenze SMVector RS-485 LECOM User Manual

Page 21

Advertising
background image

19

CMVLC401A

Commissioning

8

Drive Registers

8.1

Configuration and Control Registers

Registers #1 through #1099 are reserved for registers that are only available over the network and cannot be accessed
via the drive’s local keypad.

Table 9: Configuration & Control Registers

Code
Number

Parameter Name

Default Range of Adjustment

Important

C0040

Controller Inhibit

0

0 Controller inhibited
1 Controller enabled

The controller can also be enabled
with the control word C0135

C0043

Fault Reset

0

0 No Action
1 Reset Fault

The fault can also be reset with
the control word C0135

C0046

Frequency Setpoint

0.0

500.0 Hz

Read only

C0050

Actual Output
Frequency

0.0

500.0 Hz

Read only

C0068

Operating Status Bit
Word

Bit

Description

Read only

0-3

The 10th digit of the LECOM fault number is
displayed. Example:
TRIP OH = 5 (LECOM no. = 50)

4-7

Last communication error
0 = No fault
1 = Check sum error
2 = Protocol frame error
3 = Reserved
4 = Invalid code number
5 = Invalid variable
6 = No access permission
7 = Telegram processing interrupted by a new
telegram
15 = General fault

8

Control via LECOM enabled

9

Actual frequency above threshold C17

10

Direction of rotation
0 = CW
1 = CCW

11

Power stage transistors energized

12

Quick STOP active

13

Current Limit

14

Setpoint frequency reached

15

Fault occurred

LECOM Format = VH