Commissioning 9 programming parameters – Lenze SMVector RS-485 LECOM User Manual

Page 25

Advertising
background image

23

CMVLC401A

Commissioning

9

Programming Parameters

There is an offset of 1000 between the Drive Programming Parameter numbers and the code numbers used in the
LECOM messages. For example, if you want to read Drive Programming Parameter P103 (Maximum Frequency) over
the LECOM network, you would read code number 1103.

9.1

Fault History (P500)

Value

Display Fault Message

0

No Fault

1

TMP Output Fault

2

F.OF

Output (Transistor) Fault

3

F.OF1 Ground Fault

4

F.AF

High Drive Temperature

5

F.rF

Flying Start Fault

6

F.HF

High DC Bus Voltage

7

F.LF

Low DC Bus Voltage

8

F.PF

Motor Thermal Overload

9

F.GF

OEM Fault

10

F.IL

Illegal Setup

11

F.dbF Dynamic Brake Over Temperature

12

F.SF

Single Phase Fault

13

F.EF

External Fault

14

F.CF

Control Fault

15

F.UF

Start Error (Power loss)

16

F.cF

Incompatibility Fault

17

F.F1

Internal Fault 1 (EPM)

18

F.F2

Internal Fault 2

19

F.F3

Internal Fault 3

20

F.F5

Internal Fault 5 (stack overflow)

21

F.F5

Internal Fault 5 (stack underflow)

22

F.F6

Internal Fault 6

23

F.F7

Internal Fault 7

24

F.F8

Internal Fault 8

25

F.F9

Internal Fault 9

26

F.bF

Personality Fault

27

F.F12 Internal Fault (AD Offset)

28

F.JF

Internal Fault (Remote Keypad Lost)

29

F.AL

Assertion Level switched during Operation Fault

30

F.F4

Internal Fault 4 (FGD Missing)

31

F.F0

Internal Fault 0 (PW Missing)

32

F.FoL Follower Lost

33

F.F11 ISO Comm Fault

34

F.ntF Internal Fault (Module Communication (SPI) Timeout)

35

F.Fnr Internal Fault (FNR: Invalid Message Received)

36

F.nF1 Network Time-out

Advertising