Technical data

General data and operating conditions

2

EDK94AZHN25 DE/EN/FR/ES/IT 2.2

33

l

H1_Daten−Maße_mm

General data

Conformity and approval

Conformity

CE

2006/95/EC

Low−Voltage Directive

Approval

UR

UL 508C

Industrial Control Equipment Recognised
(file no. E132659) for USA

Protection of persons and equipment

Enclosure

EN 60529

IP00

Protective measures

Against short circuit

Mounting conditions

Mounting place

In the control cabinet

Mounting position

Vertically

Mounting clearances

Above/below

³

25 mm

To the sides

Side−by−side mounting without clearance

EMC

Noise emission

EN 61800−3

Conducted, category C2.

Noise immunity

EN 61800−3

Burst on mains cable:

2 kV/5 kHz

Burst on control cable:

2 kV/5 kHz

Surge on mains cable:

1 kV (1.2

m

s/50

m

s;

phase − phase)

2 kV (1.2

m

s/50

m

s;

phase − PE)