Electrical installation

Wiring

Connecting busbars

4

l

41

EDK94ZPM113 DE/EN/FR/ES/IT 4.0

Proceed as follows to connect the busbars:
1. If devices of the interconnected system have already been in operation:

Ensure that the power supply system is switched off by checking the
voltage at the supply terminals.

If necessary, switch off the power supply and wait at least 3 minutes.

2. Loosen the busbar screws but do not remove them completely.
3. Push the busbars as far as possible to the left towards the adjacent

busbar.

Ensure that there is good contact to the adjacent busbar.

4. Tighten the busbar screws.

Tightening torque: 3.2 ... 3.5 Nm (28 ... 31 lb−in).

5. Screw all components onto the mounting plate.

Tightening torque: 3.4 Nm (30 lb−in).