Electrical installation

Wiring
Terminal assignment

4

l

44

EDK94ZPM113 DE/EN/FR/ES/IT 4.0

1

2

SSP94IT001

Fig. 4−4

Plugging the IT insulating cap onto the earthing jumper

Proceed as follows to disconnect the internal connection between the filters
and PE:
1. Remove IT insulating cap from the parking position

 in the installation

backplane.

For this apply a screwdriver on the right or left and lever off the
insulating cap.

Optionally the insulating cap can be carefully removed using an
appropriate pliers.

2. Attach IT insulating cap to the earthing jumper

‚ until it clicks into place.

Motor

Terminal X105
(right part)

Labelling

Description

U
V
W

Connection of the motor phases

"

Functional earth
Connect the shields of the motor phases and of the
optional motor brake control separately and with a
surface as large as possible to the shield sheet. Use
EMC wire clamp or EMC shield clamp for fixing.

+

Connection for the PE conductor on the motor side
with M5 ring cable lug

SSP940X105