Electrical installation

Wiring
Design of the cables

4

l

42

EDK94ZPM113 DE/EN/FR/ES/IT 4.0

4.3.2

Design of the cables

ƒ

The cables used must comply with the approvals required for the location
(e.g. UL).

ƒ

It is imperative to comply with the regulations concerning minimum
cross−sections of PE conductors. The cross−section of the PE conductor
must be at least as large as the cross−section of the power connections.

ƒ

The effectiveness of a shielded cable is reached by:

Providing a good shield connection through large−surface shield
contact.

Using only braided shields with low shield resistance made of tin−plated
or nickel−plated copper braid.

Using braided shields with an overlap rate > 70 % and an overlap angle
of 90 °.

Keeping unshielded cable ends as short as possible.

Use system cables or shielded cables for these connections:

ƒ

Motor

ƒ

Motor holding brake (shielding is required when being integrated into the
motor cable; connection to optional motor brake control)

ƒ

Motor temperature monitoring

The following connections need not be shielded:

ƒ

DC bus

4.3.3

How to connect the shield

E94AZPS004

Fig. 4−3

Connect the shield to the shield sheet (graphics on the right: motor cable for device sizes
II and III)