4 technical data, General data and operating conditions, Technical data – Lenze E82ZAFLC001 User Manual

Page 40: 4technical data

Advertising
background image

4

Technical data

General data and operating conditions

EDK82ZAFLC−001 DE/EN/FR 5.0

40

l

H1_Daten−Einsatzbed_Klima_FIF

4

Technical data

General data and operating conditions

General data

Range

Values

Communication protocol

LECOM−A/B V2.0

Communication medium

RS485 (LECOM−B)

Character format:

7E1: 7 bit ASCII, 1 stop bit, 1 start bit, 1 parity bit (even)

Baud rate [kbit/s]

1200, 2400, 4800, 9600, 19200, 38400, 57600

LECOM−B station

Slave

Network topology

l

without repeaters: line

l

with repeaters: line or tree

Max. number of stations

Standard: 31 (= 1 bus segment) / with repeaters: 90

Max. cable length per bus segment

1000 m
(depending on baud rate and cable type used)

Communication time

l

Sum of cycle time and processing time in the fieldbus
stations. The times are independent of each other.

l

Processing time in the controller:
– Parameter data: approx. 30 ms + 20 ms tolerance
– Process data: approx. 3 ms + 2 ms tolerance

External DC voltage supply

+24 V DC ±10 %, max. 80 mA

Terminal strip X3/

VP

Level: 5 V (reference: GND3)
Load capacity: I

max

= 10 mA

28

External terminal supply
U(ext.) = +12 V DC − 0% ... +30 V DC + 0%

20

DC voltage source for internal supply of the controller inhibit (CINH)
U = + 20 V (reference: GND1),
I

max

= 10 mA

59

External function module supply
U(ext.) = +24 V DC

±

10%

Protection of persons and equipment

Type of protection

EN 60529

IP20

Advertising