Voltage supply

)

Note!

Always use a separate power supply unit in every control cabinet and safely
separate it according to EN 61800−5−1 ("SELV"/"PELV") in the case of external
voltage supply and larger distances between the control cabinets.

DC voltage supply

Internal

The internal voltage is provided at terminal X3.3/20. It serves to supply the
controller inhibit (CINH).

External

The external voltage supply of the function module is required if communication is
to be maintained during a failure of the standard device supply.

X3/

Designation

Function

Level

+

Additional HF−shield termination

A

T/R(A)

RS485 data line A

B

T/R(B)

RS485 data line B

CN

CNTR

*)

During data transmission:
CNTR = HIGH
+5 V (reference: GND3)

VP

*)

+5 V (reference: GND3)

40

GND3

Reference potential for LECOM−B
network *)

7

GND1

Reference potential for the internal
supply at X3/20

39

GND2

Reference potential of controller inhibit
(CINH) at X3/28

28

CINH

Controller inhibit

l

Start = HIGH (+12 ... +30 V)

l

Stop = LOW (0 ... +3 V)

20

DC voltage source for internal supply of
controller inhibit (CINH)

+20 V (reference: GND1)

59

External DC supply for the function
module

U(ext.) = +24 V DC

±

10%

(reference: GND1)

*) e.g. if a repeater is connected