Wiring of the lecom-b network, Wiring of the lecom−b network, Electrical installation – Lenze E82ZAFLC001 User Manual

Page 49

Advertising
background image

Electrical installation

Wiring of the LECOM−B network

6

EDK82ZAFLC−001 DE/EN/FR 5.0

49

l

H2_verdraht_LECOM−LeitungsspezRS485

Wiring of the LECOM−B network

Basic structure of a LECOM−B network

3

3

3

S

S

S

1

2

2

2

0 m

1000 m

E82ZAFL005

No.

Element

Comment

1

Master computer

E.g. PC or PLC with RS485 master interface module

2

Bus cable

Max. length: 1000 m

3

LECOM−B slave

Standard device applicable with E82ZAFLC0xx function
module

Specification of the transmission cable

Specification of transmission cable for RS485

l

Total cable length up to 300 m:

Cable type

LIYCY 1 x 2 x 0.5 mm

2

shielded

Cable resistance

£ 40 W/km

Capacitance per unit length

£ 130 nF/km

l

Total cable length up to 1200 m:

Cable type

CYPIMF 1 x 2 x 0.5 mm

2

shielded

Cable resistance

£ 40 W/km

Capacitance per unit length

£ 130 nF/km