Electrical installation
Wiring according to EMC
6
EDK82ZAFLC−001 DE/EN/FR 5.0
45
l
H1_E_INST−VorgehenVerdraht
6
Electrical installation
Wiring according to EMC
For wiring according to EMC requirements observe the following points:
)
Note!
ƒ
Separate control cables/data lines from motor cables.
ƒ
Connect the shields of control cables/data lines at both ends in the case of
digital signals.
ƒ
Use an equalizing conductor with a cross−section of at least 16 mm
2
(reference: PE) to avoid potential differences between the bus nodes.
ƒ
Observe the other notes concerning EMC−compliant wiring given in the
documentation for the standard device.
Wiring procedure
1. Observe bus topology, so do not use any stubs.
2. Follow the wiring notes given in the documentation for the control system.
3. Only use cables which comply with the specifications listed (
^ 49).
4. Follow the notes on the voltage supply for the function module (
5. Activate the bus terminating resistors on the first and last physical node (