Possible settings by interbus master, 5commissioning – Lenze EMF2113IB User Manual

Page 66

Advertising
background image

5

Commissioning

Possible settings by INTERBUS master

EDKMF2113 DE/EN/FR 5.1

66

l

H1inbet−Merker_hidden statusanzeige

Possible settings by INTERBUS master

)

Note!

If switches (S1 ... S8) remain in the Lenze setting OFF, the configurations set
under the codes C1910, C1911 and C1912 will become active when the device
is switched on.

Switch off the voltage supply of the communication module and afterwards on again to
activate changed settings.

Please note:
ƒ Impermissible settings are indicated by the yellow LED (communication) (

^ 69).

ƒ As a maximum, the data word sum (PCD + PCP) is to amount to 10 words.
ƒ Index determination: 24575 − Lenze code number (Cxxxx)

Codes for configuration

Code

Values

Explanation

C1910

2 ... 20 (1 ... 10 words)

Number of process data bytes
(2 process data bytes = 1 process data
word)

C1911

0: AIF−CTRL device control

Operation with AIF−CTRL device control
or
operation with DRIVECOM profile 21

1: DRIVECOM control

C1912

Number of
parameter data
words (PCP)

ID code

Number of parameter data words (PCP)

0

0x03

1

0xE3

2

0xE0

4

0xE1