6 technical data, General data and operating conditions, Technical data – Lenze EMF2113IB User Manual

Page 70: 6technical data

Advertising
background image

6

Technical data

General data and operating conditions

EDKMF2113 DE/EN/FR 5.1

70

l

H1_Daten−AlleMaßeInMM

6

Technical data

General data and operating conditions

Field

Values

Communication media

RS485

Network topology

Ring

Communication profile

PCP 2.0

Drive profile

DRIVECOM profile 21

INTERBUS node

Slave

Baud rate

l

500 kbits/s

l

2 Mbits/s

External voltage supply

Values

"+"

U = 24 V DC (21.6 V − 0% ... 26.4 V + 0 %)

I = 120 mA

"−"

Reference potential for external voltage supply

Ambient conditions

Climatic conditions

Storage 1 K3 to IEC/EN 60721−3−1

− 25 °C ... + 60 °C

Transport 2 K3 to IEC/EN 60721−3−2

− 25 °C ... + 70 °C

Operation 3 K3 to IEC/EN 60721−3−3

0 °C ... + 55 °C

Degree of pollution

2 to IEC/EN 61800−5−1

Enclosure

IP20