Technical data
Protective insulation
EDKMF2113 DE/EN/FR 5.1
73
l
H1_Daten−AlleMaßeInMM
Protocol data
Field
Values
Maximum number of
controllers
Dependent on INTERBUS master (e.g. Phoenix Contact G4 master).
For the following data, always the smaller value applies dependent
on the fact, whether PCP communication is available or not:
l
with PCP communication:
62 or
l
without PCP communication:
256/number of PD
Process data words (PD)
1 ... 10 (selectable)
Lenze setting: 2 words
Parameter data words (PCP)
0, 1, 2, 4
Lenze setting: 1 word
Maximum number of data
words
As a maximum, the data word sum (PD + PCP) is to amount to 10
words.
INTERBUS ID
(module ID)
Module ID for set length
3
= 0x03
PCP, 0 words
227
= 0xE3
PCP, 1 word
224
= 0xE0
PCP, 2 words
225
= 0xE1
PCP, 4 words
Maximum PDU length
64 bytes
Supported PCP services
Initiate, Abort, Status, Identify, Get−0V−long, Read, Write