Electrical installation

Bus cable length

6

EDK82ZAFUC010 DE/EN/FR 4.0

59

l

H2 BusLeitgsLaenge−Leitungslaenge_3

3. Compare the two values determined.

If the value given in Tab. 2 is smaller than the required total cable length from Tab. 1,
repeaters must be used. Repeaters divide the total cable length into segments.

)

Note!

ƒ

Note the reduction of the total cable length due to the signal delay of the
repeater (see example

^ 60

).

ƒ

Mixed operation
– There is mixed operation if different nodes are connected to the same

mains.

– If the total cable lengths of the nodes are different at the same baud

rate, the smaller value must be used to determine the max. cable
length.

Example: Selection help

Given:

l

Cable cross−section:

0.5 mm

2

(according to cable specification

^ 57)

l

Number of nodes
connected:

100

l

Repeater:

Lenze repeater, type 2176 (cable reduction: 30 m)

For the above selections the following cable lengths / number of repeaters must be
observed:

Baud rate [kbps]

10

20

50

125

250

500

1000

Max. cable length [m]

8000

3900

1500

630

290

120

25

Segment cable length [m]

270

270

270

270

290

120

25

Number of repeaters

33

16

6

2