Commissioning
Setting node address and baud rate
EDK82ZAFUC010 DE/EN/FR 4.0
72
l
H2_set_node_addr_baud−Ueb−rate Hinweis
Baud rate setting
ON
1
6
2
7
4
3
8
5
9 10
ON
OFF
Fig. 2
Baud rate setting
)
Note!
The baud rate must be set to the same value for all controllers and the master
computer.
Baud rate [kbps]
S8
S9
S10
10
ON
ON
OFF
20
ON
OFF
ON
50
OFF
ON
ON
125
OFF
ON
OFF
250
OFF
OFF
ON
500
OFF
OFF
OFF
1000
ON
OFF
OFF
Automatic recognition
ON
ON
ON
Automatic recognition of the baud rate
)
Note!
The baud rate can only be recognised automatically if other nodes are already
sending telegrams via the CAN bus without errors:
ƒ
After switch−on or "Reset Node" the function module searches for the
correct baud rate by analysing the telegrams sent by the other nodes.
ƒ
If the correct baud rate is recognised, it is accepted by the function module.