Electrical installation
Assignment of the terminals
EDK82ZAFUC010 DE/EN/FR 4.0
63
l
H2_BelegungAnschlKlemmen−klemmbesch−010
Assignment of the terminals
Terminal
X3 1/
Designation
Function / level
CG
CAN−GND
Reference potential for CAN
CL
CAN−LOW
CAN data line (LOW)
CH
CAN−HIGH
CAN data line (HIGH)
Terminal
X3 2/
Designation
Function / level
59
External DC voltage supply for the function module
l
+24 V DC
±
10% (reference: GND1)
l
Current consumption at 24 V DC: 80 mA
The current flowing to other bus nodes via terminal 59 when looping
through the supply voltage must not exceed 3 A.
7
GND1
Reference potential for X3.3/20
Terminal
X3 3/
Designation
Function / level
7
GND1
Reference potential for X3.3/20
39
GND2
Reference potential 2 of the controller inhibit (CINH) at X3.3/28
28
CINH
Controller inhibit
l
Input resistance: 3.3 k
W
l
Start = HIGH (+12 ... +30 V)
l
Stop = LOW (0 ... +3 V)
(reference: GND2)
20
DC voltage source to the external supply of the controller inhibit
(CINH)
l
+20 V (ref: GND1)
l
I
max
= 10 mA