Assignment of the terminals, Electrical installation – Lenze E82ZAFUC010 User Manual

Page 63

Advertising
background image

Electrical installation

Assignment of the terminals

6

EDK82ZAFUC010 DE/EN/FR 4.0

63

l

H2_BelegungAnschlKlemmen−klemmbesch−010

Assignment of the terminals

Terminal

X3 1/

Designation

Function / level

CG

CAN−GND

Reference potential for CAN

CL

CAN−LOW

CAN data line (LOW)

CH

CAN−HIGH

CAN data line (HIGH)

Terminal
X3 2/

Designation

Function / level

59

External DC voltage supply for the function module

l

+24 V DC

±

10% (reference: GND1)

l

Current consumption at 24 V DC: 80 mA

The current flowing to other bus nodes via terminal 59 when looping
through the supply voltage must not exceed 3 A.

7

GND1

Reference potential for X3.3/20

Terminal
X3 3/

Designation

Function / level

7

GND1

Reference potential for X3.3/20

39

GND2

Reference potential 2 of the controller inhibit (CINH) at X3.3/28

28

CINH

Controller inhibit

l

Input resistance: 3.3 k

W

l

Start = HIGH (+12 ... +30 V)

l

Stop = LOW (0 ... +3 V)
(reference: GND2)

20

DC voltage source to the external supply of the controller inhibit
(CINH)

l

+20 V (ref: GND1)

l

I

max

= 10 mA