Electrical installation

Bus cable length

EDK82ZAFUC010 DE/EN/FR 4.0

60

l

H2 BusLeitgsLaenge−Leitungslaenge_3

Check repeater application

Given:

l

Baud rate:

125 kbps

l

Cable cross−section:

0.5 mm

2

l

Number of nodes
connected:

28

l

Cable length:

1500 m

Procedure

Cable length

See

1. Total cable length at 125 kbps:

630 m

Tab. 1

2. Segment cable length for 28 nodes and a cable cross−section

of 0.5 mm

2

:

360 m

Tab. 2

3. Comparison: The value under item 2 is smaller than the required cable length of 1500 m.

Conclusion

l

It is not possible to use a cable length of 1500 m without applying a repeater.

l

After 360 m (item 2.), a repeater must be installed.

Result

l

The Lenze repeater, type 2176 (cable reduction: 30 m), is used

l

Calculation of the max. cable length for the
– first segment: 360 m
second and every further segment: 360 m (according to Tab. 1) minus 30 m (cable reduction if

a repeater is used)

à Maximum possible cable length with four repeaters: 1680 m.

à Thus it is possible to use the required cable length.

)

Note!

The use of a further repeater is recommended as

ƒ

Service interface
Advantage: Trouble−free connection during running bus operation is
possible.

ƒ

Calibration interface
Advantage: Calibration/programming device remains isolated.