Cable cross-sections and screw-tightening torques, Cable cross−sections and screw−tightening torques, 6electrical installation – Lenze E82ZAFUC010 User Manual
Page 64
![background image](/manuals/565940/64/background.png)
Electrical installation
Cable cross−sections and screw−tightening torques
EDK82ZAFUC010 DE/EN/FR 4.0
64
l
H2_LtgQuer+AnzMom−Steckerleiste_Federkraft
Cable cross−sections and screw−tightening torques
Field
Values
Electrical connection
Plug connector with double screw connection
Possible connections
rigid:
1.5 mm
2
(AWG 16)
flexible:
without wire end ferrule
1.5 mm
2
(AWG 16)
with wire end ferrule, without plastic sleeve
1.5 mm
2
(AWG 16)
with wire end ferrule, with plastic sleeve
1.5 mm
2
(AWG 16)
Tightening torque
0.5 ... 0.6 Nm (4.4 ... 5.3 lb−in)
Stripping length
10 mm
Field
Values
Electrical connection
2−pin plug connector with spring connection
Possible connections
rigid:
1.5 mm
2
(AWG 16)
flexible:
without wire end ferrule
1.5 mm
2
(AWG 16)
with wire end ferrule, without plastic sleeve
1.5 mm
2
(AWG 16)
with wire end ferrule, with plastic sleeve
1.5 mm
2
(AWG 16)
Stripping length
9 mm