Drive setup & operation, 4mc drive setup & operation – Lenze MC Series Drives User Manual

Page 10

Advertising
background image

RG-MCMOD

6

Drive Setup & Operation

4

MC Drive Setup & Operation

4.1 Serial Address

All AC Tech drives have a Serial Address Parameter that must be programmed prior to attempting to
operate the serial interface (Programming Parameter #58 / AC Tech Register #109).
TIP - Avoid using address 1. Most Modbus devices ship with a default address of 1. As duplicate addressing
on a Modbus network is not allowed, this can lead to conflicts when replacing and commissioning nodes.
To avoid this it is recommended that you do not set the slave address to 1.

4.2 Serial Communications Parameter

All AC Tech drives have a Serial Communications Parameter that governs the operation of the Serial Link.
On MC drives this is #57 SERIAL LINK (register #108). Table 4 lists the selections for MC Parameter 57,
SERIAL LINK.

Table 4: MC Parameter 57 Selections

Setting

Description

Watchdog Timeout Period

00

DISABLE

01

WITH TIMER

10 sec

02

WITHOUT TIMER

Explanation of Terms:

• DISABLED

serial link not operational

• WITH TIMER

serial link allows reading & writing of both control & programming parameters.
Watchdog timer is enabled (refer to section 4.6,

Watchdog Timer

).

• WITHOUT TIMER serial link allows reading & writing of both control & programming parameters.

Watchdog timer is disabled (refer to section 4.6,

Watchdog Timer

).

Prior to attempting to communicate with the drive, Serial Communications Parameter must be appropriately
programmed.

4.3 Control Parameter

The Control Parameter on MC drives (Programming Parameter #30 / AC Tech Register #81) determines
how much control a user has over a drive via the serial link. The Control Parameter must be appropriately
programmed for a particular application. Refer to the MC Series Installation and Operation Manual (M101
or M301, respectively) for a detailed explanation on programming the drive parameters.

TIP - For most serial applications, CONTROL is set to LOCAL on the MC1000 and SERIAL on the MC3000.
Refer to Table 5 for Control settings.