20

Drive Control & Communication

6

MC Programming Parameters

6.1 Format

NOTE - Attention
Parameter list presented in Section 6.2 is valid only for MC Software revision 213-083.
For revisions, refer to appropriate MC1000 (M101) or MC3000 (M301) Manual.

Abbreviations:

SA

(1byte) drive address (1-247)

RA

(1byte) register address

CRCH (1 byte) Cyclic Redundancy Check High
CRCL (1 byte) Cyclic Redundancy Check L

READING:

Message structure for reading 1 word: (most of parameters)

Request: SA 03 00 RA 00 01

CRCH CRCL

Response: SA 03 02 DH DL CRCH CRCL

Message structure for reading 4 word: (Reg. #100 Fault history and #101 Software Version)

Request: SA 03 00 RA 00 04 CRCH CRCL
Response: SA 03 08 D1H D1L D2H D2L D3H D3L D4H D4L CRCH CRCL

WRITING:

Message structure for writing 1 word: (all parameters)

Request: SA 06 00 RA DH DL CRCH CRCL
Response: SA 06 00 RA DH DL CRCH CRCL

LEGEND for Parameter List
1st Column:

AC Tech Register #

MC Register # followed by Hex value in parenthesis: 51 (33H)

2nd Column:

Parameter

1

= Drive's programming parameter number

2

= MC1000 without PID (SW version 213-083, revision 13 or older)

3

= MC1000 with PID

4

= MC3000

4th Column:

Range of Adjustment The Modbus values are whole numbers. One decimal place is

assumed. A superscript

5

denotes parameter where two decimal

places are assumed.
For example, to program a value of 28.20 Hz, the user can program
28.20 into the MC drive and the drive will display 28.20 but for
Modbus communications, the user must input 2820. The one
decimal place is assumed. If the user wanted a value of 282 Hz,
then for Modbus communications he would have to input 28200.

5th Column:

Default Value

5

= Two decimal places assumed (hundredths)