Register
Number
(hexadecimal
representation)

Parameter

1

Parameter Name

Range of Adjustment
Modbus value (decimal value)

Factory Default

103 (67)
104 (68)
105 (69)

52

3,4

53

3,4

54

3,4

TB14OUT
TB15OUT
RELAY

00 - None
01 - Run
02 - Fault
03 - /Fault
04 - Lock
05 - @ Speed
06 - Above #3
07 - I Limit
08 - Auto/Man
09 - Follower Present

10 - Min/Max
11 - /Min/Max
12 - Min Alarm
13 - /Min Alarm
14 - Max Alarm
15 - /Max Alarm
16 - Reverse
17 - Sleep
18 - SPD = 0Hz

00 - None

106 (6A)

55

3,4

TB5B LOSS

00 - Fault
01 - SP#4
02 - None

00 - Fault

108 (6C)

57

SERIAL

00 - Disable
01 - w/ Timer
02 - w/o Timer

00 - Disable

109 (6D)

58

ADDRESS

1 - 247

30

112 (70)

61

PASSWORD

0000 - 9999

0019

114 (72)

63

SOFTWARE

(View Only)

(N/A)

115 (73)

64

MONITOR

00 - OFF
01 - ON

01 - ON

116 (74)

65

PROGRAM

00 - Maintain
01 - Reset 60
02 - Reset 50
Refer to Note 10

01 - Reset 60

117 (75)

66

HISTORY

00 - Maintain
01 - Clear

00 - Maintain

121 (79)

70

3,4

PID MODE

00 - Off
01 - Normal
02 - Reverse

00 - Off

125 (7D)

74

3,4

PID FB

00 - TB-5A
01 - TB-5B

00 - TB-5A

126 (7E)

75

3,4

FB @ MIN

0 - 65000

0 (0.0%)

127 (7F)

76

3,4

FB @ MAX

0 - 65000

65000 (100%)

129 (81)

78

3,4

I GAIN

0 - 100 (0.0 - 10.0 sec)

0 (0.0 sec)

130 (82)

79

3,4

D GAIN

0 - 100 (0.0 - 10.0 sec)

0 (0.0 sec)

131 (83)

80

3,4

PID ACC

0 - 1000 (0.0 - 100.0 sec)

300 (30.0 sec)

132 (84)

81

3,4

MIN ALRM

FB @ MIN - FB @ MAX

0.0%

133 (85)

82

3,4

MAX ALRM

FB @ MIN - FB @ MAX

0.0%

149 (95)

69

2

98

LANGUAGE

Refer to Note 11

English

150 (96)

70

2

99

3,4

FAULT HISTORY

(View Only)

(N/A)

1 = Drive's programming parameter number; 2 = MC1000 without PID (SW ver 213-083, rev 13 or older); 3 = MC1000 with PID; 4 = MC3000