Troubleshooting and fault elimination, Display of operating data, diagnostics, Display of operating data – Lenze EVF9326−xV User Manual

Page 32: 4troubleshooting and fault elimination

Advertising
background image

Troubleshooting and fault elimination

Display of operating data, diagnostics
Display of operating data

4

l

32

EDKVF93−01 EN 3.0

4

Troubleshooting and fault elimination

4.1

Display of operating data, diagnostics

4.1.1

Display of operating data

Description

Important operating parameters are measured by the controller. They can be displayed
with the keypad or PC.

Some operating data can be calibrated to be displayed or selected directly with the unit of
the process quantity (e.g. pressure, temperature, speed).

)

Note!

The calibration always affects all specified codes simultaneously.

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze

Selection

C0051

MCTRL−NACT

−36000

{1 rpm}

36000 Actual speed value, function block

MCTRL

l

Read only

C0052

MCTRL−Umot

0

{1 V}

800 Motor voltage, function block MCTRL

l

Read only

l

MCTRL−VACT = 100 % = C0090

C0053

UG−VOLTAGE

0

{1 V}

900 DC−bus voltage, function block MCTRL

l

Read only

l

MCTRL−DCVOLT = 100 % = 1000 V

C0054

IMot

0.0

{0.1 A}

500.0 Current motor current, function block

MCTRL

l

Read only

l

MCTRL−IACT = 100 % = C0022

C0061

Heatsink temp

0

{1 °C}

100 Heatsink temperature

l

Read only

l

If the temperature of the heatsink
> 85 °C, the controller sets TRIP

OH

l

Early warning is possible via

OH4,

temperature is set in C0122

C0063

Mot temp

0

{1 °C}

200 Motor temperature

l

Read only

l

Monitoring of the motor
temperature must be activated.

l

KTY at X8/5, X8/8:
– At 150 °C, TRIP

OH3 is set

– Early warning is possible via

OH7,

temperature is set in C0121

l

PTC, thermal contact at T1, T2:
– Release sets TRIP or warning

OH8