Troubleshooting and fault elimination

Troubleshooting
Status display via controller LEDs

4

l

34

EDKVF93−01 EN 3.0

4.2

Troubleshooting

Detecting breakdowns

A breakdown can be detected quickly via the LEDs at the controller or via the status
information at the keypad.

Analysing errors

Analyse the error using the history buffer. The list of fault messages gives you advice how
to remove the fault. (

40)

4.2.1

Status display via controller LEDs

During operation the operating status of the controller is shown by 2 LEDs.

LED

Operating status

Red



Green

‚

Off

On

Controller is enabled

On

On

Mains is switched on and automatic start is
inhibited

Off

Blinking slowly

Controller is inhibited

Off

On

Motor data identification is being performed

Blinking quickly

Off

Undervoltage

Blinking slowly

Off

Active fault

Advertising