Troubleshooting and fault elimination

System error messages
General error messages

4

l

40

EDKVF93−01 EN 3.0

Adjustment

U

DC

t C0912

³

t < C0912

t = C0912



‚

0

1

IMP

9300vec142

Fig. 4−2

Influence of the delay time (C0912)



Switch−off threshold OU

‚

Switch−on threshold OU

0

The period of time between exceeding the switch−off threshold OU and undershooting the
switch−on threshold OU equals or is higher than the delay time set in C0912.
After undershooting the switch−on threshold OU, the pulse inhibit is deactivated.

1

The period of time between exceeding the switch−off threshold OU and undershooting the
switch−on threshold OU is lower than the delay time set in C0912.
The pulse inhibit is deactivated after the delay time in C0912 has elapsed.

ƒ

The delay time in [ms] is set under C0912. The Lenze setting can be changed by the
factor 0.5 ... 2.

4.5

System error messages

4.5.1

General error messages

)

Note!

In the case of a query via system bus (CAN), the fault messages are
represented as numbers (see first column of the table).