Troubleshooting and fault elimination, System error messages general error messages – Lenze EVF9326−xV User Manual

Page 42

Advertising
background image

Troubleshooting and fault elimination

System error messages
General error messages

4

l

42

EDKVF93−01 EN 3.0

Remedy

Cause

Description

Fault message

Remedy

Cause

Description

Display

No.

x032

LP1

Motor phase failure

A current−carrying motor phase
has failed.

l

Check motor.

l

Check motor cable.

l

Switch off monitoring
(C0597 = 3).

The current limit value is set too
low.

l

Set higher current limit value
via C0599.

0050

OH

Heatsink temperature > +90

C

Ambient temperature
T

u

> +40

C or > +50 C

l

Allow module to cool and
ensure better ventilation.

l

Check ambient temperature in
the control cabinet.

Heatsink is very dirty.

Clean heatsink.

Wrong mounting position

Change mounting position.

x053

OH3

Motor temperature
> +150

C threshold

(temperature detection via
resolver or incremental value
encoder)

Motor is thermally overloaded
due to:

l

Impermissible continuous
current

l

Frequent or too long
acceleration processes

l

Check drive dimensioning.

l

Switch off monitoring
(C0583 = 3).

No PTC/temperature contact
connected.

Correct wiring.

x054

OH4

Heatsink temperature > C0122

Ambient temperature T

u

> +40

C

or > +50

C

l

Allow module to cool and
ensure better ventilation.

l

Check ambient temperature in
the control cabinet.

l

Switch off monitoring
(C0582 = 3).

Heatsink is very dirty.

Clean heatsink

Wrong mounting position

Change mounting position.

The value specified under C0122
is set too low.

Enter a higher value under C0122.

x057

OH7

Motor temperature > C0121
(temperature detection via
resolver or incremental value
encoder)

Motor is thermally overloaded
due to:

l

Impermissible continuous
current

l

Frequent or too long
acceleration processes

l

Check drive dimensioning.

l

Switch off monitoring
(C0584 = 3).

No PTC/temperature contact
connected.

Correct wiring.

The value specified under C0121
is set too low.

Enter a higher value in C0121.

x058

OH8

Motor temperature via inputs T1
and T2 is too high.

Motor is thermally overloaded
due to:

l

Impermissible continuous
current

l

Frequent or too long
acceleration processes

l

Check drive dimensioning.

l

Switch off monitoring
(C0585 = 3).

Terminals T1 and T2 are not
connected

Connect PTC/temperature
contact.

x061

CE0

Automation interface (AIF)
communication error

Faulty transfer of control
commands via AIF.

l

Plug in the communication
module/keypad XT firmly,
screw down, if necessary.

l

Switch off monitoring
(C0126 = 3).

Advertising
This manual is related to the following products: