Troubleshooting and fault elimination

Fault elimination

Behaviour in case of overvoltage in the DC bus (OU message)

4

l

39

EDKVF93−01 EN 3.0

4.4.3

Behaviour in case of overvoltage in the DC bus (OU message)

Description

If the DC−bus voltage (U

DC

) exceeds the switch−off threshold OU, the pulse inhibit is set. At

the same time, an internal timing element starts for a delay time (C0912).

The pulse inhibit is deactivated if the voltage falls below the switch−on threshold OU and
the delay time has elapsed.

Switching thresholds in case of overvoltage in the DC bus (OU):

Mains voltage range

C0173

Switch−off threshold OU

Switch−on threshold OU

< 400 V

Operation with / without
brake chopper

0

770 V

755 V

400 V

Operation with / without
brake chopper

1

*

770 V

755 V

460 V

Operation with / without
brake chopper

2

770 V

755 V

480 V

Operation without brake
chopper

3

770 V

755 V

480 V

Operation with brake
chopper

4

800 V

785 V

*

Lenze setting

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze

Selection

C0912

OV delay time

à

{1 ms}

− Delay time of the pulse enable after

an OU message

à

Depending on C0082, C0086,
C0087, C0088, C0089, C0090,
C0091, C0092
A change of one of the codes
resets C0912 to the time of the
selected motor

l

The time is derived from the
double rotor time constant