Product description

Variants

MC−PNC, MC−PND

3

l

21

BA_MC−Card EN 1.0

Technical data

MC−PNC, MC−PND

Conformity, approval, directive

Conformity

CE

EN 61000−6−4
EN 61000−6−2

EMC Directive Class A,
industrial premises

Approval

UR

UL 508
CSA C22.2

Process Control Equipment
(File−No. E236341)

Directive

RoHS

Products lead−free in accordance with CE
Directive 2011/65/EU

General data and operating conditions

See standard device

Electrical data

Current

< 0.2 A

at standard device supply voltage of 24 V

Electrical isolation to the
fieldbus

yes

Mechanical data

Mass

< 0.1 kg

MC−PNC (controller)

I/O data

l

Configurable up to max. 5760 bytes input

l

Configurable up to max. 5760 bytes output

Data transport

l

Ethernet frames

Communication

l

PROFINET IO−RT
– cyclic and acyclic

Acyclic data

l

Read, write, record: max. 1 kbyte/request

l

Alarms

Functions

l

Cyclic process data

l

Buffering host−controlled data exchange of cyclic data

l

Minimum cycle time: 1 ms

l

Different cycle times are configurable for different devices

l

Max. 32 devices can be configured

l

DCP

l

Context management via CL−RPC

l

One buffer is available per device for diagnostic data

Special features

l

No support for
– RT over UDP
– Multicast communication
– DHCP

l

Only one IOCR1 per IO device is possible, IOCR data length:
1024 bytes

l

Max. number of the connectable IO devices decreases to
25 when cycle times lower than 4 ms are used.

l

NameOfStation of the IO controller cannot be set via the
DCP Set NameOfStation service but only by the
configuration during the start