Mc-isi, Mc−isi, Electrical installation – Lenze MC−xxx Card User Manual

Page 30

Advertising
background image

Electrical installation

Wiring and Configuration
MC−ISI

4

l

30

BA_MC−Card EN 1.0

4.3.3

MC−ISI

Configuration

DIP switch for setting the mode:

DIP switch

Description

1 2 3 4

ON

Pos. 1 = ON: RS485 mode
Pos. 2 = ON: RS422 mode
Pos. 3 = ON/OFF: four−wire conductor/two−wire conductor (only relevant for RS485 mode)
Pos. 4 = ON/OFF: echo function activated/deactivated (only relevant for RS485 mode +
two−wire conductor)

MC−ISI_004

Set the mode:

Mode

DIP switch setting

RS485 mode, two−wire conductor, deactivated echo function (default)
RS485 mode, two−wire conductor, activated echo function
RS485 mode, four−wire conductor
RS422

Pos. 1 = ON
Pos. 1+4 = ON
Pos. 1+3 = ON
Pos. 2 = ON

)

Note!

ƒ

If switch 1 = ON (RS485), switch 2 must be set to OFF;
if switch 2 = ON (RS422), switch 1 must be set to OFF.

ƒ

The echo function monitors the RS485 bus for collisions.

Further settings:

MC−ISI_003

Jumper Function

JP1

plugged−on to ENA: default setting

JP3

plugged−on to HW: default setting

JP5

plugged−on: terminating resistor for RS422−/485 mode activated
open: terminating resistor for RS422−/485 mode deactivated

Do not assign JP2! Lenze service personnel only.