5.1 Abbreviations

Table 7 lists the abbreviations used in Table 6

Tmd Drive Control Registers:

Table 7: Abbreviations

Abbreviation

Description

R

Read

W

Write

RS

Response

SA

Slave Address (typically 01 through F7 hex)

CRCH

Cyclic Redundancy Check High byte

CRCL

Cyclic Redundancy Check Low byte

DH

Data High byte

DL

Data Low byte

Tmd#

Tmd Register # (Modbus Register numbers are 1 larger)

5.2 Drive Control - Register #1

Table 8 illustrates the Data High Byte and Data Low Byte format of Register #1, Drive Control.

Table 8: Drive Control - Register #1

Data Low Byte

0

UPDATE BUFFERS

1

LOCK SECURITY

2

STOP DRIVE (COAST TO STOP)

3

START DRIVE

4

UNUSED

5

UNUSED

6

SET REVERSE

7

SET FORWARD

Data High Byte

8

NETWORK SPEED REFERENCE

9

LOCAL SPEED REFERENCE

10
11
12
13
14
15

The appropriate bit is set to 1. For example, to stop the drive bit two is set (send 0004H). To start the drive
send 0008H. Setting update buffers bit, enables to start the drive using downloaded data. Locking security
disables the serial drive control, the communications watchdog timer and prevents any further writing to
control or parameter registers.