RG-TDMOD 16

Drive Control & Communication

NOTE 4b - Actual Speed (Register #24 Bytes D2H and D2L or Register #25)
• In tenths of a Hz
• Most significant byte is first, followed by Least significant

NOTE 4c - Load (Register #24 Byte D3H or Register #26 DH)
• In percent of full load
• Example: 64 (one byte in hex) ==> 100 in decimal ==> 100% (drive load).

5.5.2 Operational Status - Register #26

Table 12 lists the Operational Status (Register #24 byte D3L or Register #26 DL)

Table 12: Operational Status

Bit

Parameter

0

FAULT LOCKOUT

1

FAULT

2

START PENDING

3

MOTOR CALIBRATION NOT DONE

4

STOP

5

LOWER TRANSISTORS SWITCHING ON

6

MOTOR CALIBRATION ENABLED

7

RUN AT 0Hz

8

RUN

9

ACCEL

10

DECEL

11

DECEL OVERRIDE

12

DC BRAKE

13

FLYING START

14

SLOW CURRENT LIMIT

15

FAST CURRENT LIMIT

16

OFF

17

INHIBIT

5.5.3 Actual Rotational Direction - Registers #24 & 27

Table 13 lists the Actual Rotational Direction (Register #24 byte D4H or Register #27 DH).

Table 13: Actual Rotational Direction

Setting

Direction

0

FORWARD

1

REVERSE