Drive control & communication, 4 basic drive status – Lenze Tmd Series Drives Modbus Communications User Manual

Page 33

Advertising
background image

29 RG-TDMOD

Drive Control & Communication

7.4 Basic Drive Status

AC Tech register 24 is a 6 word entity containing the drive’s status information. To read the entire status
block use Modbus function code 3 with a length of 6 to read starting at Modbus register number 40025.
The low byte of the third word in this block of data contains the operational status. If this is the only data
you want you can use Modbus function code 3 with a length of 1 to read register 40027.

The value of that low byte of data corresponds to the following operational states:

Table 20: Operational Status

Bit

Parameter

0

FAULT LOCKOUT

1

FAULT

2

START PENDING

3

MOTOR CALIBRATION NOT DONE

4

STOP

5

LOWER TRANSISTORS SWITCHING ON

6

MOTOR CALIBRATION ENABLED

7

RUN AT 0Hz

8

RUN

9

ACCEL

10

DECEL

11

DECEL OVERRIDE

12

DC BRAKE

13

FLYING START

14

SLOW CURRENT LIMIT

15

FAST CURRENT LIMIT

16

OFF

17

INHIBIT