Drive Control & Communication

5.5.7 Present Fault - Registers #24 & 29

Table 16 lists the Present Fault (Register #24 byte D6H of Register #29 DH)

Table 16: Present Fault

Setting Fault

Display

Setting Fault

Display

0

NO FAULT

18

INTERNAL FAULT 1 (EPM)

F1

1, 2

OUTPUT (TRANSISTOR) FAULT

OC1

19

INTERNAL FAULT 2

F2

3

EARTH FAULT

OC2

20

INTERNAL FAULT 3

F3

4

RESERVED

21, 22

INTERNAL FAULT 5

F5

5

OVER TEMPERATURE FAULT

OH

23

INTERNAL FAULT 6

F6

6

FLYING RESTART FAULT

rF

24

INTERNAL FAULT 7

F7

7

OVER VOLTAGE FAULT

OU

25

INTERNAL FAULT 8

F8

8

UNDER VOLTAGE FAULT

LU

26

INTERNAL FAULT 9

F9

9

MOTOR OVERLOAD FAULT

OC6

27

IDENTIFICATION FAULT

bF

10

OEM DATA FAULT

GF

28

A/D CONVERTER FAULT

Ad

11

CONFIGURATION FAULT

CFG

29

REMOTE KEYPAD FAULT

JF

12

DYNAMIC BRAKE OVERHEATED FAULT

dF

30

LOSS OF 4-20mA SIGNAL

Sd5

13

SINGLE PHASE FAULT

SF

31

COMMUNICATION FAULT

FC5

14

EXTERNAL FAULT

EEr

32

INTERNAL FAULT 4

F4

15

CONTROL FAULT

CF

33

LOSS OF MOTOR PHASE

LP1

16

AUTOMATIC START INHIBITED

LC

34

INTERNAL FAULT 10

Fo

17

INCOMPATIBILITY FAULT

cF

5.5.8 Commanded Rotational Direction - Registers #24 & 29

Table 17 lists the Commanded Rotational Direction (Register #24 byte D6L or Register #29 DL)

Table 17: Commanded Rotational Direction

Setting

Direction

0

FORWARD

1

REVERSE

5.6 Motor Volts - Register #30

Output Voltage to the motor is expressed in volts (V). It is not expressed as a percentage of the nominal
drive voltage.