Drive control & communication – Lenze SCF Series Drives Modbus Communications User Manual
Page 18
![background image](/manuals/566279/18/background.png)
RG-SFMOD 14
Drive Control & Communication
5.4.2 Operational Status - Register #26
Table 10 lists the Operational Status (byte D3L or Register #26 DL)
Table 10: Operational Status
Setting
Parameter
0
FAULT LOCKOUT
1
FAULT
2
START PENDING
3
STOP
4
DC BRAKE
5
RUN AT 0Hz
6
RUN
7
ACCEL
8
DECEL
9
CURRENT LIMIT
10
DECEL OVERRIDE
11
LOWER TRANSISTORS SWITCHING ON
5.4.3 Actual Rotational Direction - Registers #24 & 27
Table 11 lists the Actual Rotational Direction (Register #24 byte D4H or Register #27 DH).
Table 11: Actual Rotational Direction
Setting
Direction
0
FORWARD
1
REVERSE
5.4.4 Control Mode - Registers #24 & 27
Table 12 lists the Control Mode (Register #24 byte D4L or Register #27 DL).
Table 12: Control Mode
Setting
Control
Operation
0
TERMINAL
Start/Stop operation controlled from the drive's control board terminal strip
1
REMOTE KEYPAD Start/Stop operation controlled from remote keypad
2 or 3
SERIAL
Start/Stop operation controlled via serial link