Drive control & communication – Lenze SCF Series Drives Modbus Communications User Manual

Page 26

Advertising
background image

RG-SFMOD 22

Drive Control & Communication

AC Tech
Register
Number
(hexadecimal
representation)

Parameter

1

Parameter Name

Range of Adjustment
Modbus value (decimal value)

Factory Default

92 (5CH)

42

Accel / Decel #2

1 – 36000 (0.1 sec – 3600.0 sec)

200 (20.0 sec)

93 (5DH)

43

Serial Address

1 - 247

1

94 (5EH)

44

Password

000 - 999

225

45

Not Used

46

Not Used

97 (61H)

47

Clear History

01 - Maintain
02 - Clear

01 - Maintain

98 (62H)

48

Program Selection

01 - User Settings
02 - OEM Settings
03 - Reset OEM
04 - Reset 60
05 - Reset 50

04 - Reset 60

99 (63H)

49

Not Used

Diagnostic – Read Only Parameters! (50# - 60#)
100 (64H)

50

FAULT HISTORY

Must Read 4 Words (Read Only)

See Note [5]

101 (65H)

51

SOFTWARE VERSION

Must Read 1 or 4 Words (Read Only)

See Note [6]

102 (66H)

52

BUS VOLTAGE [%]

0-250 (MIN 0% MAX 250%)

Read Only

103 (67H)

53

ACTUAL MOTOR
VOLTAGE [%]

0-250 (MIN 0% MAX 250%)

Read Only

104 (68H)

54

MOTOR LOAD [%]

0-250 (MIN 0% MAX 250%)

Read Only

105 (69H)

55

0-10VDC analog input
[100% = 10VDC]

0-250 (MIN 0% MAX 250%)

Read Only

106 (6AH)

56

4-20mA analog input
[100% = 20mA]

0-250 (MIN 0% MAX 250%)

Read Only

107 (6BH)

57

DIGITAL I/O

SERIAL READ - DIGITAL I/O REPRESENTATION

See Note [7]

108 (6CH)

58

DIGITAL I/O

SERIAL READ - DIGITAL I/O REPRESENTATION

See Note [7]

109 (6DH)

59

ANALOG OUTPUT TB30
[100% = 10VDC]

0-250 (MIN 0% MAX 250%)

Read Only

110 (6EH)

60

ANALOG OUTPUT TB31
[100% = 10VDC]

0-250 (MIN 0% MAX 250%)

Read Only

1

= Drive's programming parameter number