Drive control & communication – Lenze SCF Series Drives Modbus Communications User Manual

Page 24

Advertising
background image

RG-SFMOD 20

Drive Control & Communication

AC Tech
Register
Number
(hexadecimal
representation)

Parameter

1

Parameter Name

Range of Adjustment
Modbus value (decimal value)

Factory Default

60 (3CH)

10

TB-13A Input

01 - None
02 - 0-10 VDC
03 - 4-20 mA
04 - Preset Speed #1
05 - Run Reverse
06 - Start Reverse
07 - External Fault
08 - Remote Keypad Control
09 - Dynamic Brake Fault
10 - Ramp To Stop
11 - Accel / Decel #2

01 - None

61 (3DH)

11

TB-13B Input

01 - None
02 - 0-10 VDC
03 - 4-20 mA
04 - Preset Speed #2
05 - Decrease Freq (MOP)
06 - Jog Forward
07 - Jog Reverse
08 - Ramp to Stop

01 - None

62 (3EH)

12

TB-13C Input

01 - None
02 - 0-10 VDC
03 - 4-20 mA
04 - Preset Speed #3
05 - Inc Freq (MOP)
06 - External Fault
07 - Remote Keypad Control
08 - Dynamic Brake Fault
09 - Accel / Decel #2

01 - None

63 (3FH)

13

TB-15 OC Output

01 - None
02 - Run
03 - Fault
04 - Inverse Fault
05 - Fault Lockout
06 - At Set Speed
07 - Above Preset #3
08 - Current Limit
09 - Auto Speed (speed source via terminal strip)
10 - Reverse (rotation direction indication)

01 - None

64 (40H)

14

Control

01 - Terminal Strip Only
02 - Remote Keypad Only
03 - Selectable at Terminal

01 - Terminal Strip