L-force | plc designer – Lenze PLC Designer PLC Designer (R2-x) User Manual
Page 368

L-force | PLC Designer
The Resources
366
DMS 3.2 EN 02/2011 TD29
Identification
Station address (see 'Properties of the DP masters'), Station name (matches
device name, editable)
Activation
Slave is active/inactive in current configuration. If activation is not selected,
configuration data will still be transferred to the coupler on Download, but
not data exchange occurs over the bus.
Watchdog If
Watchdog Control is set active, the entered Watchdog time applies
(access monitoring, basis 10 ms). If the slave has not been accessed by the
master within this time, it is reset to its initialization state.
You can inspect the corresponding GSD-file via the GSD-file button.
In-/outputs of a DP slave
Dialog for configuring the in-/outputs of a DP slave
The way in which the configuration of a DP slave is done, depends on whether it is a
'modular' or a 'non-modular', 'fix' slave.