HPU Setup

Model 505G2.20 - 505G2.30 SilentFlo™ HPU

Installation

33

Aux Contact: On/Off/Temp
Aux Polarity Normal/Reverse

Pushbuttons /Indicators.

Aux Contact: On/Off - gray

Aux Contact: Temp - black

Aux Polarity Normal - gray

Aux Polarity Reverse - black

One of the auxiliary contacts can be used to control an external

device such as a warning lamp or a remote cooling circuit. The

auxiliary contact controls whether the contact is active whenever a
pump motor is running (Aux Contact: On/Off - gray) or

whenever a pump motor is running and the temperature of the

hydraulic fluid in the reservoir reached the trip temperature (Aux
Contact: Temp
- black).

Press the Aux Contact: button to display Aux Contact:
On/Off
to activate the contact when at least one pump
motor is running, and to deactivate when no pump
motors are running.

Press the Aux Contact: button to display Aux Contact:
Temp
to activate the contact when at least one pump
motor is running and the fluid temperature in the
reservoir is above the temperature trip level and to
deactivate the contact when either the temperature is
lower than the temperature trip level or no pump motors
are running.

Press the Aux Polarity: button to display Aux Polarity:
Normal
to cause the contact to close when it is active.
MTS Controllers use normal polarity.

Press the Aux Polarity: button to display Aux Polarity:
Reverse
to cause the contact to open when it is active.

The other Aux contact is set for motor pump running only. Its

function and polarity are not selectable.