GX-94 Operator’s Manual

Page 6

1 Alarms are user adjustable. See

Viewing and Setting Alarms

in the setup mode section.

Table 2: Sensor/Channel Specifications

Combustible Gas

(HC)

Oxygen

Hydrogen

Sulfide

Carbon

Monoxide

Detection
Range

0 - 100% LEL

0 - 40.0%

0 - 100.0 ppm 0 - 500 ppm

Display
Increments

1% LEL

0.1%

0.5 ppm

1 ppm

Low Alarm

1

10% LEL

19.5%
(decreasing)

10.0 ppm

25 ppm

High Alarm

1

50% LEL

23.5%
(increasing)

----

----

TWA Alarm

1

----

----

10.0 ppm

25 ppm

STEL
Alarm

1

----

----

15.0 ppm

400 ppm

Detection
Principle

Catalytic
Combustion

Electrochem-
ical (gal-
vanic type)
Cell

Electrochemi-
cal Cell

Electrochem-
ical Cell

Ceiling
Alarm

---

----

Off

Off

Accuracy

0 - 20% LEL

± 2% LEL

21% - 100% LEL
± 5% LEL

± 0.5% Oxy-
gen

0 - 30 ppm
±1.5 ppm

31 - 100 ppm
±5 ppm

0 - 50 ppm
±5 ppm

51 - 150 ppm
± 15 ppm

151 - 500
ppm
± 25 ppm